ISOMETER IRDH275

Insulation monitoring device for
AC, AC/DC and DC systems (IT systems)

 

Product description:

The ISOMETER® of the IRDH275 series is designed to monitor the insulation resistance of unearthed main circuits (IT systems) AC, AC/DC 0…793 V resp. DC 0…650 V. The AMPPlus measurement method meets the particular requirements of modern power supplies which often include rectifiers, converters, thyristor-controlled DC drives and directly connected DC components. In these systems often high leakage capacitances against earth occur due to interference suppression measures. The IRDH275 automatically adapts itself to the existing system conditions. In combination with a coupling device, the devices can also be used for higher voltages. An external supply voltage allows de-energised systems to be monitored too. For door mounting into distribution panels, refer to type IRDH375(B).

Application:

• AC, DC or AC/DC main circuits
• AC/DC main circuits with directly connected DC components, such as rectifiers, converters, and thyristor-controlled DC drives
• UPS systems, battery systems
• Heaters with phase control
• Installations including switch-mode power supplies
• IT systems including high leakage capacitances
• Coupled IT systems

Device features:

• Insulation monitoring for unearthed AC, AC/DC systems 0…793 V, DC 0…650 V
• Nominal voltage extendable via coupling device
• Two separately adjustable response values1 kΩ…10 MΩ
• AMPPlus measurement method
• Automatic adaptation to the system leakage capacitance
• Info button to display device settings and system leakage capacitance
• Self monitoring with automatic alarm
• Automatic self test, selectable
• Connection for external kΩ indication
• Test and reset button
• External test/reset button can be connected
• Two separate alarm relays with two potential-free changeover contacts
• N/O or N/C operation, selectable
• Backlit LC display
• RS-485 interface

Wiring diagram:

Dimension:

 

Operating elements:

Technical data: 

 

 Ordering information: