RCMS460

Multi-channel AC, pulsed DC and AC/DC sensitive
residual current monitors for earthed AC, DC
and AC/DC systems (TN and TT systems)

 

Product description:

The RCMS system consists of one or more RCMS460-D/-L or RCMS490-D/-L residual current monitors, which are able to detect and evaluate fault, residual and operating currents in earthed power supplies via the related measuring current transformers. The maximum voltage of the system to be monitored depends on the nominal insulation voltage of the measuring current transformer used in the case of busbar systems, resp. depend on the cables or conductors that are routed through.
Closed W…AB series measuring current transformers are required to measure AC/DC sensitive residual currents (according to IEC/TR 60755: Type B). Six W…AB series measuring current transformers require one AN420 or AN110 power supply unit. W (closed), WR (rectangular), WS (split-core) and WF… (flexible) series measuring current transformers are used for alternating and pulsating currents (according to IEC/TR 60755: Type A).
Any combination of the various measuring current transformer series can be connected to the monitor measuring channels. Each RCMS460-D/-L and RCMS490-D/-L has 12 measuring channels. Up to 90 residual current monitors can be connected via a BMS bus (RS-485 interface with BMS protocol), thereby up to 1080 measuring channels (sub-circuits) can be monitored.
If this product is to be used for personnel, fire or plant protection, the frequency response can be set accordingly. The measured currents can be analysed for harmonics.

Typical application:

Measuring and evaluating residual, fault and rated currents of loads and installations in the frequency range of 0…2000 Hz (W…AB series measuring current transformers), 42…2000 Hz (W, WR, WS WF series measuring current transformers).
• Monitoring of currents regarded as fire hazards in flammable atmospheres
• EMC monitoring of TN-S systems for “stray currents” and additional N-PE connections.
• Monitoring of N conductors for overload caused by harmonics
• Monitoring of PE and equipotential bonding conductors to ensure they are free of current
• Residual current monitoring of stationary electrical equipment and systems to determine test intervals which meet practical requirements in compliance with the accident prevention regulations BGV A3 (Germany).
• Personnel and fire protection due to rapid disconnection
• Monitoring of digital inputs

Device features:

• Optional AC, pulsed DC or AC/DC sensitive measurement by selecting the respective measuring current transformer for each channel
• True r.m.s. value measurement
• 12 measuring channels per device for residual current measurement or digital input
• Up to 90 RCMS… monitors, up to1080 measuring channels in the system
• Fast parallel scanning for all channels
• Response ranges:
10 mA…10 A (0…2000 Hz),
6 mA…20 A (42…2000 Hz),
100 mA…125 A (42…2000 Hz) RCMS…-D4
• Preset function
• Adjustable time delays
• The frequency response characteristics can be set for the protection of persons, fire and plant protection
• History memory with date and time stamp for 300 data records
• Data logger for 300 data records/channel
• Analysis of the harmonics, DC, THF
• Two alarm relays with one changeover contact each
• Device version RCMS490 with one alarm contact per channel
• N/O or N/C operation and fault memory selectable
• Connection external test/reset button
• Backlit graphical display
(7-segment display) and alarm LEDs
• Data exchange via BMS bus
• Password protection for device setting
• Continuous CT connection monitoring
• RoHS compliant

Wiring diagram: 

Dimension: 

 

Technical data:  

 

Ordering information: